Friction Measurement and Display

This page only shows measurements and alarms . The configurations are

done on the Friction page under Parameter .
The Load Factor Values show the present Measured Value and drag

pointers for the Minimum Value, Maximum Value and the Average Value

over time .
The Alarm Factor Alarm Limits as well as the Load Factor / Friction Alarms

on this page are just for information and need to be configured on

the configuration page . These alarms are activated once the average

measurement has exceeded the alarm thresholds defined under the

upper and lower limit .

Set Reference Value (Set Ref. )
This function allows setting a fingerprint of a certain stem friction level (Average Reference) with a time stamp (Reference Time)

for the hours in operation . To set the Friction Reference click on the Set Ref. button . Then the Average Value in connection with

the time-stamp (Reference Time) is saved to the positioner . To ensure that the positioner has saved the data, click on Update .

Message

Status

Description / Explanation

Recommended Action

High Friction Alarm

Service / Maintenance Required

The friction of the Stem packing

has increased and causes the stem

movement to change beyond the

specified maximum value .

Please check the packing for

irregularities . Maybe the packing is

just too tight . Loosen the packing

and use the Audit Trail to inspect the

movement .

Low Friction Alarm

Service / Maintenance Required

The friction of the Stem- packing

has reduced and causes the stem

movement to change below the

specified minimum value .

Please check the packing for a

possible leakage . Tighten the packing

and use the Audit Trail to inspect the

movement .

Friction History

The Friction History shows a Histogram displaying the duration of the

average friction measurement over time . The duration is illustrated in

percent of the total time . The vertical line in the middle of the Friction

History shows the Reference Value (Average Value) within a variation of

+/–5% .
The columns of the Histogram identify two states: To the left a decrease

in friction (Less) and to the right an increase in friction (More) is

displayed . Color coding from green (=OK) to yellow (=Maintenance

Required) and red (=Failure) indicate the state of the friction .
The reference column shows the average value +/- 5% . The columns to

both sides show friction changes such as:
Less: –5 to –25%, –25 to –50% and –50 to –100% decrease in friction
More: 5 to 25%, 25 to 50% and 50 to 100% increase in friction

Configuration / Parameter

Page 58

August 2014

POS-UM-00011-EN-02