Write Protect
Enable/Disable Write Protection for Valve Parameters
An active write protection secures the local push buttons from an unauthorized access . The following procedures show how a
write protection can be activated and deactivated .
Activating a Write Protection
1 . Go to Additional functions >
Management > Write Protect.
The Wizard will open and
show the actual status: The
device is not write protected.
2 . Press Continue .
The Wizard shows: The device
is now write protected.
De-activating the Write Protection
1 . Go to Additional functions >
Management > Write Protect.
The Wizard will open and
show the actual status: The
device is write protected .
2 . Press Continue .
The Wizard shows: The device
is now not write protected.