Badger Meter SRD/SRI Valve Positioners User Manual

Page 76

Advertising
background image

Friction / Load Factor

Friction Measurement

This page only shows measurements and alarms . The configurations are

done on the Friction page under Parameter .
The Load Factor Values show the present Measured Value and drag

pointers for the Minimum Value, Maximum Value and the Average Value

over time .
The Alarm Factor Alarm Limits as well as the Load Factor / Friction Alarms

on this page are just for information and need to be configured on

the configuration page . These alarms are activated once the average

measurement has exceeded the alarm thresholds defined under the

upper and lower limit .

Set Reference Value (Set Ref.)

This function allows setting a fingerprint of a certain stem friction level (Average Reference) with a time stamp (Reference Time)

for the hours in operation . To set the Friction Reference:
1 . Click the Set Ref. button . This saves the Average Value in connection with the time-stamp (Reference Time) to the

positioner .

2 . To ensure that the positioner has saved the data, click Update .

Message

Status

Description / Explanation

Recommended Action

High Friction Alarm Service / Maintenance Required

The friction of the Stem packing

has increased and causes the stem

movement to change beyond the

specified maximum value .

Check the packing for irregularities .

Maybe the packing is just too tight .

Loosen the packing and use the Audit

Trail to inspect the movement .

Low Friction Alarm Service / Maintenance Required

The friction of the Stem packing has

reduced and causes the stem movement

to change below the specified minimum

value .

Check the packing for a possible

leakage . Tighten the packing and use

the Audit Trail to inspect the movement .

Friction History

The Friction History shows a Histogram displaying the duration of the average friction measurement over time . The duration

is illustrated in percent of the total time . The vertical line in the middle of the Friction History shows the Reference Value

(Average Value) within a variation of +/–5% .
The columns of the Histogram identify two states: To the left a decrease in friction (Less) and to the right an increase in friction

(More) is displayed . Color coding from green (=OK) to yellow (=Maintenance Required) and red (=Failure) indicate the state of

the friction .
The reference column shows the average value +/– 5% . The columns to both sides show friction changes such as:
• Less: –5…–25%, –25…–50% and –50…–100% decrease in friction
• More: 5…25%, 25…50% and 50…100% increase in friction

Diagnostics

Page 76

August 2014

POS-UM-00011-EN-02

Advertising