Badger Meter SRD/SRI Valve Positioners User Manual

Page 75

Advertising
background image

Response History

The Response History is a Histogram that shows the control behavior of

the actuator/valve in percentage over time .
The histogram is divided into 5 segments, each representing a

specific control behavior . This allows identifying if an actuator/valve is

predominantly in a steady state, transient, offset for instance if there is a

constant control deviation between the setpoint and the valve position

or if its unstable .

The exact percentage of each response behavior is identified by the values listed above the histograms .
• Offline . This value is increased if the positioner is powered up, but the Autostart has not been activated yet, or the

positioner has manually been put into the device status Offline .

• Steady . This value is increased if the positioner is in control, but not moving . The setpoint and the valve position are

constant at a certain value . See Position History for exact valve position .

• Transient . This value is increased if the positioner is online and constantly moving .
• Offset . This value is increased if the positioner identifies a deviation between the setpoint and the valve position, greater

than the specified control deviation configured under alarms .

• Unstable . This value is increased if the positioner is continuously oscillating around a constant setpoint . An Unstable

behavior in the control can occur, if there’s a leakage in the actuator diaphragm, a leakage in the output-pressure

connection between the positioner and the actuator or if the stem-lock or coupling is shifting .

The Response History can display 4 different History Intervals . These Historians allow seeing the response behavior up to the

last 60 months . The 4 Historians can be configured under Configuration/Maintenance/History Interval .
Response History with Combo Box

Diagnostics

Page 75

August 2014

POS-UM-00011-EN-02

Advertising