Diagnostic status, Detailed technical information – Badger Meter SRD/SRI Valve Positioners User Manual

Page 85

Advertising
background image

• Bit 0 – Currently in fail safe time out . No setpoint commands have been sent from the controlling system for the entire

time out period . The positioner only fail safes when it is on-line . So, communication from the host have ceased . Most

probable cause is that the host or FBM has been taken off-line or the connection has been broken .

DIAGNOSTIC STATUS

In general, an error bit raised here indicates a serious problem in the positioner and probably requires replacement .

Message

Explanation

Recommended Action

RAM

Error Writing positioner memory .

Replace failed item or positioner .

EEPROM

Error Writing positioner EEPROM .

Replace failed item or positioner .

ROM

Error Writing positioner ROM .

Replace failed item or positioner .

AD Converter

Converter function not controllable .

Replace failed item or positioner .

Actuator OOR

Position is not within permissible range (-5% . . . +105%) .

Check mechanics of actuator and valve .

Perform Endpoints Calibration .

Current Loop

I/P Motor

Connection of I/P converter to electronic board failed .

Replace failed item or positioner .

Potentiometer Connection of potentiometer to electronic board failed .

Replace failed item or positioner .

Option Board

Option Board not configured or failed .

Check configuration or

replace failed option board .

Detailed Technical Information

15

14

13

12

11

10

9

8

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

7

6

5

4

3

2

1

0

NOT USED

Pot Fail

Current Loop Out of range ADC not finish

RAM Error

EEPROM Error

ROM Error

• Bit 6 – Potentiometer use has failed; the positioner no longer accurately controls the valve . (Fatal) .
• Bit 5 – Current loop to I/P-Motor broken . (Fatal) .
• Bit 4 – The actuator is out of range . Position is unreliable or not being properly controlled . (Fatal) .
• Bit 3 – Analog to Digital conversion won’t finish . (Fatal) .
• Bit 2 – Access to positioner read addressable memory (RAM) resulted in an error . If all the data in the configuration pages

looks correct, the positioner is probably still functional .

• Bit 1 – Access to positioner EEPROM resulted in an error . Positioner is incapable of storing configuration information or

saving data . (Non-fatal)

• Bit 0 – Access to positioner ROM resulted in an error . Positioner software is now unreliable . (Fatal) .
RAM Diagnostic Bit 0
Access to positioner read only memory resulted in an error . Positioner must be replaced because the software is no

longer reliable .
EEPROM Diagnostic Bit 1
Access to positioner EEPROM resulted in an error . Positioner is incapable of storing configuration or saving data . It will still run

until the next cycling of power, but should be replaced at the earliest opportunity .
ROM Diagnostic Bit 2
Access to positioner read addressable memory (RAM) resulted in an error . RAM is used to initialize data . If all the data in the

configuration pages looks correct, the positioner is probably still functional . It should be replaced at the earliest opportunity,

however .

Diagnostic Status

Page 85

August 2014

POS-UM-00011-EN-02