Calibration Status
Message
Status
Description / Explanation
Recommended Action
No Autostart done
—
No Autostart was done or Autostart was
run and did not complete successfully .
Ensure proper mounting of positioner and
adequate supply pressure . Refer to online Help
for other potential causes . Rerun Autostart
Calibration procedure .
Invalid Configuration Maintenance Required
Invalid configuration .
Correct configuration, perform Restore Factory
Settings, rerun Autostart procedure .
Input Loop Trim
Maintenance Required
Input signal requires calibration .
Perform Analog Setpoint Calibration
procedure .
Feedback Trim
Maintenance Required
Feedback unit requires calibration .
Perform Angle Calibration procedure .
Diagnostics
Page 71