Badger Meter SRD/SRI Valve Positioners User Manual

Page 71

Advertising
background image

Calibration Status

Message

Status

Description / Explanation

Recommended Action

No Autostart done

No Autostart was done or Autostart was

run and did not complete successfully .

Ensure proper mounting of positioner and

adequate supply pressure . Refer to online Help

for other potential causes . Rerun Autostart

Calibration procedure .

Invalid Configuration Maintenance Required

Invalid configuration .

Correct configuration, perform Restore Factory

Settings, rerun Autostart procedure .

Input Loop Trim

Maintenance Required

Input signal requires calibration .

Perform Analog Setpoint Calibration

procedure .

Feedback Trim

Maintenance Required

Feedback unit requires calibration .

Perform Angle Calibration procedure .

Diagnostics

Page 71

August 2014

POS-UM-00011-EN-02