Srd-dtm – Badger Meter SRD/SRI Valve Positioners User Manual

Page 94

Advertising
background image

Profibus Control Panel

The Profibus Control panel is under Start > Control Panel > PROFIBUS .
Make sure that you see a green √ in front of the Node . If you see

something other than that, such as a red x, the PROFIcard is not active .

Contact Softing for assistance .

SRD-DTM

Connect the SRD-DTM for Profibus as shown below and described

in

“Opening a Project” on page 13

.

After selecting the device driver from the device catalog, a window

automatically opens for editing the bus address for this specific unit .

The default slave address is 126 .
The following addresses are reserved for the Master or default:

0, 1 and 126 .

After selecting the bus address, each line will show the address for the

Master and Slave first . See the following example:

<0, PROFIdtm>PROFIdtm DPV1

(0: Node 0)

<50, Tag Number> SRD991 V2 (PBDPV1)

(50: Bus Address)

Profibus Configurations

Page 94

August 2014

POS-UM-00011-EN-02