Binary Input

The Binary Input is used for externally operating two independent

binary switches . These switches are connected to the two inputs which

are supplied by the basic device . The binary inputs can be used for

diagnostics or also configurable for the control functions . The enclosed

table shows the control functions of the switches .

Switch 1

Switch 2

Actuator Control Function

close

close

normal operation

open

close

go to top at 0%

close

open

go to stop at 100%

open

open

hold last position

Configure Binary Input Signal
Both switches need to be closed (bridged) for normal operation . If one of each switch is opened, the positioner will move to

one designated valve position . If both switches are open (not bridged), the positioner will Hold Last Value .
Input 1 Active
There are two functions that can be activated for the Binary Input .
If the function Goto 0% is activated and the binary contact is operated, the valve will move to the 0% valve position . If the

function Set Status Binary Input is activated and the binary contact is operated, a status bit will be execute and displayed

under Process/Binary Input .
Both functions can be activated separately or together .
The operation of the Binary Input ignores travel limits and is predominate to the setpoint signal .
Input 2 Active
There are two functions that can be activated for the Binary Input .
If the function Goto 100% is activated and the binary contact is operated, the valve will move to the 100% valve position . If

the function Set Status Binary Input is activated and the binary contact is operated, a status bit will be execute and displayed

under Process/Binary Input .
Both functions can be activated separately or together .
The operation of the Binary Input ignores travel limits and is predominate to the setpoint signal .
Input 1 Active and Input 2 Active
There are two functions that can be activated for each Binary Input .
If the function Goto 0% and Goto 100% is activated and the binary contact is operated, the valve will Hold Last Value of the

valve position . If the function Set Status Binary Input is activated and the binary contacts are operated, a status bit will be

execute and displayed under Process/Binary Input .
Both functions for each switch can be activated separately or together .
The operation of the Binary Input ignores travel limits and is predominate to the setpoint signal .
Binary Input
The value Binary Input allows defining the kind of contact used for activating these actions or the alarm . The Binary Input can

be used as a Limit Switch for protection against overflow of tanks or for an emergency operation to close the valve .

Message

Status

Description / Explanation

Recommended Action

Binary Input (Freely definable)

INFO

An external mechanical switch

has activated the Binary Input .

Depending on the reason for

activating switches

Configuration / Parameter

Page 51

August 2014

POS-UM-00011-EN-02

Advertising