Partial Stroke Test

The Partial Stroke Test (PST) is used for testing of the ESD capabilities of

safety shutdown valves . Since the safety-related valves are always fully

open and do not move within normal operation, it is very important to

identify if a valve would close, in case the safety system shuts down the

valves .
For this purpose the PST is used . It lets you manually or automatically

stroke the valve by applying a configurable Setpoint Change and a Max.

Wait Time for Position Change .
Once the PST is activated and a Setpoint Change is configured at,

for example, 10% and the Max. Wait Time for Position Change to, for

example, 30 seconds, the positioner will move the valve at 10% from

the fully open 100% to approximately 90% valve position .

If the valve does not move instantly, the positioner will wait for 30 seconds to move the valve . After the test in finished, the

positioner will generate a Testing Status . The Testing Status can be retrieved by pressing Update .
The test will result in displaying a Partial Stroke Test Status showing the different states such as Not Done, Running, Restricted,

OK or Error . If the PST has failed the display will show Maintenance, to identify the operator of a failure .
Activation of Partial Stroke Test
The Partial Stroke Test can only be activated if the setpoint and the valve position is greater than 99% . If the setpoint and the

valve position is below 99% the Testing Status: Restricted will be shown .
Automatic
The Partial Stroke Test can be set to Automatic, by checking the box . In this case the Time Interval has to be set to the value,

after what time the test shall be repeated . The table shows some rough time-intervals . For example, the Time Interval is

configured with 4380 hours . In this case every 4380 hours a Partial Stroke Test is executed . If the setpoint and the valve

position is below 99% the Testing Status: Restricted will be shown .

Years

Months

Days

Hours

0 .5

6

182 .5

4380

1

12

365

8760

2

24

730

17520

3

36

1095

26280

4

48

1460

35040

5

60

1825

43800

10

120

3650

87600

Manual
Press the Start button to execute the Partial Stroke Test . The Test will then perform a Setpoint Change with a Max. Wait Time for

Position Change as configured .
Time Interval
The Time Interval has to be set to the value, after what time the Partial Stroke Test shall be repeated, when the Test is set to

Automatic . The table shows some rough time-intervals . For example, the Time Interval is configured with 4380 hours . In this

case, every 4380 hours a Partial Stroke Test is executed .
The interval can be configured between 0 .1 to x hours . The value is preset to 8760 hours .
Setpoint Change
The Setpoint Change is the percentage of the valve movement from the fully open valve position . If this value is set, for

example, to 10%, the Setpoint Change will move the valve from fully open at 100% to 90% valve position .