Badger Meter SRD/SRI Valve Positioners User Manual

Page 42

Advertising
background image

Custom Curve

The Custom Curve lets you define up to 22 input/output pairs . To add a

new pair of values:
1 . Select Custom .
2 . Enter the X-Value and Y-Value .
3 . Click Add .
The input value pair will be sorted in increasing order of the X-Values . To

modify a value pair:
1 . Select the X-Value in the list box .
2 . Modify the value and press Modify .
To delete a value pair, select the X-Value in the list box and press

Delete .

A custom curve which is stored in the device can be activated by selecting Custom or deactivated by switching to Linear,

Equal Percentage (1:50) or Quick Open (50:1) .

NOTE:

N

The flow characteristics of the valve depend on both the positioner and valve trim characteristics . For example, if

the positioner Characteristic is set to Linear and the valve has an Equal percentage trim, then (Cv/Cv .max) vs . input

signal will also be Equal percentage .

Number of Points
This is a single byte field . You can specify how many straight line segments will comprise the characterization curve . If custom

characterizer is enabled, this value sets the number of points . The default value is 2 (one line segment) . This is also the

minimum . If one of the standard options is selected, the custom points are disabled and turned off .
Select Point
Use this Combobox to select the Points for output and input .
Xn Characterizer Input Value
This is a 4-byte real that is used as the input to the custom characterizer function . It is only enabled if the characterization is

custom, not for any other option . Xn and Yn represent the input signal and the valve position respectively . Between Xn and

Xn+1, a straight line interpolation of Yn to Yn+1 is defined . Similarly, between Xn-1 and Xn, a straight line interpolation of Yn-1

to Yn is developed . Xn must be larger than Xn-1 .
Yn Characterizer Output Value
This is a 4-byte real that is used as the input to the custom characterizer function . It is only enabled if the characterization is

custom, not for any other option . Xn and Yn represent the input signal and the valve position respectively . Between Xn and

Xn+1, a straight line interpolation of Yn to Yn+1 is defined . Similarly, between Xn-1 and Xn, a straight line interpolation of Yn-1

to Yn is developed . Xn must be larger than Xn-1 .
Characterization
This is a single-byte field . The Valve’s position characteristic is determined here . There are four options:
• Linear
• Equal percentage
• Quick opening (inverse equal percentage)
• Custom
If you choose Custom characterization, you can freely define up to 22 points to create a new characteristic for the setpoint

changes . Linear is the default .

Configuration / Parameter

Page 42

August 2014

POS-UM-00011-EN-02