The SRD991 Status Overview screen was modified to be simpler with

a focus on the most important . This concept still includes status bits

in green (√) = good and red (X) = alarm, and in addition colored tabs,

highlighting the different areas where the alarm is active .
After 02 .09 .2005

Combined Alarms

Message

Combination of Messages

Status

Description / Explanation

Recommended Action

Message 1

Message 2

Valve Stuck

High Friction

Alarm

Control Diff OOL Fault / Device

Failure

This Alarm indicates a critical

state for the operation of the

device.
The friction of the Stem

packing has increased to a

level that the valve movement

is blocked and causes a

remaining control deviation .

The valve needs to be

inspected immediately .

Pneumatic

Failure

Supply- Pressure

Alarm

Control Diff OOL Fault / Device

Failure

This Alarm indicates a critical

state for the operation of the

device.
The supply pressure has

failed and caused a remaining

control deviation .

Check if the filters are

obstructed .
Restore the supply pressure

and check the control

behavior .

Actuator Leakage

/ Pneumatic

Failure

Output- Pressure

Alarm

Control Diff OOL Fault / Device

Failure

This Alarm indicates a critical

state for the operation of the

device.
The supply pressure can

be measured, but the

valve cannot be moved .

The positioner identifies a

remaining control deviation .

Check the pneumatics and the

piping to the actuator .

Failsafe

Power Supply

Low

Fault / Device

Failure

This Alarm indicates a critical

state for the operation of the

device.
The power supply is below the

specified range and causes the

valve to go in failsafe .
Power Supply below allowed

limit .
4…20 mA / HART:

Operation below 3 .6 mA
Fieldbus / FoxCom: Operation

below 9 mA

Correct the Power Supply to

the specified minimum limits .
4…20 mA / HART:

Minimum operating value

to turn off the alarm is > 3 .8

mA . The minimum specified

current is 4 mA .
Fieldbus:

Minimum operating value:

≈10 .5 mA ± 0 .5 mA (voltage

range 9…2V DC)
FoxCom:

Minimum operating value: ≈ 9

mA at 24V DC .

Diagnostics

Page 68

August 2014

POS-UM-00011-EN-02