Process Status

Message

Status

Description / Explanation

Recommended Action

Temperature

High

Out of

Specification

Temperature above allowed limit .

Operation outside temperature limit (>80° C, 176° F) may

damage positioner components and violate electrical safety

certification requirements . Stop operating positioner .

Temperature

Low

Out of

Specification

Temperature below allowed limit .

Operation outside temperature limit (<40° C, 40° F) may damage

positioner components and violate electrical safety certification

requirements . Stop operating positioner .

Power Supply

High

Out of

Specification

Power Supply above allowed

limit . 4…20 mA / HART: Operation

above 22 mA Fieldbus / FoxCom:

Operation above 12 mA

Operation outside power supply limit (see PSS for details) may

damage positioner components and violate electrical safety

certification requirements . Stop operating positioner . Ensure that

the maximum power allowed supply is supplied to the unit .

Power Supply

Low

Out of

Specification

Power Supply below allowed limit .

4…20 mA / HART: Operation below
3 .8 mA
Fieldbus / FoxCom: Operation below
9 mA

Operation below power supply limit (see PSS for details) may

cause the positioner to go into failsafe . The communication to

the control system might be disturbed . Ensure that the minimum

power supply is supplied to the unit .

Air Supply

Pressure Alarm

Service /

Maintenance

Required

The Air Supply Pressure falls below

the configured Lower Limit .

Check if the adequate supply pressure is applied .

Output Pressure

Alarm

Service /

Maintenance

Required

The positioner cannot regulate the

Output Pressure .

Check pneumatics . Check tubing to the actuator . Check for

leakages caused by the diaphragm .

Drag Pointer

for Maximum

Temperature

Shows the maximum measured

temperature during operation .

Shows the exact value of the maximum temperature ever

measured to ensure that the High Temperature limits

(>80° C, 176° F) are not reached .

Drag Pointer

for Minimum

Temperature

Shows the minimum measured

temperature during operation .

Shows the exact value of the minimum temperature limit ever

measured to ensure that the Low Temperature limits

(<40° C, 40° F) are not reached .

Partial Stroke

Testing

The Partial Stroke Testings allows

to evaluate if an Emergency

Shutdown Device (ESD) will

operate in case of a safety

shutdown .

The Partial Stroke Test can be found under the Configuration/

Partial Stroke . This is where the Test can be configured and

activated . The Testing Status shows the evaluation of the test .

Testing Status

Good

Not Done

A Partial Stroke Test has not been executed yet .

Good

Running

Test has been started and is in progress .

Local Operation Restricted

Test is restricted . Either the valve is in control or the valve is not

fully open (100%) .

Good

OK

Test performed OK . The ESD capabilities have been tested and

showed that the valve is not stuck . The valve would move if a

safety system would close the valve .

Failure

Error

Test showed Error . The ESD capabilities cannot be guaranteed .

The valve is stuck and cannot move . The valve needs to be

inspected immediately!