3 Description of function

BU 0510 GB-3911

Subject to technical alterations

25

3.2.2.3

Resetting absolute encoders

With the exception of SSI encoders, absolute encoders can be set to the value "0" or to the value set in P609 [-
02] "Offset Position" via the functions "Reference Point Run"(see 3.2.1.1).

However, the precision of resetting the encoder position greatly depends on the actual speed of movement,
the bus load, the baud rate (CANopen encoders) and the type of encoder. Therefore it is urgently
recommended that absolute encoders are only reset when they are at a standstill.

With an SSI encoder the position can only be changed via a position offset P609 [-03]. Resetting ("Reset
position" / "Reference Point Run") is not possible.

If both an incremental encoder and an absolute encoder are connected to the frequency inverter, both
encoders are reset by performing the functions "Reference Point Run" or "Reset Position".

3.2.2.4

Parameterisation on the frequency inverter

Communication settings

If a CANopen absolute encoder is used for position detection, the CAN baud rate (P514) and the CAN
address (P515)
must be parameterised on both the encoder and the frequency inverter.

NOTE

If an IO extension (e.g. SK TU4-

IOE) is also used, it must be noted that the addresses 10 …

13 and 20 … 23 are reserved for this module (For details see Manual BU0200).

After this, the CAN Bus must be supplied with 24V in order to activate communication between all the
connected participants.
For all other absolute encoders such as Endat, SSI, … (SK 540E and above), no communication settings are
required between the frequency inverter and the associated encoder.

Encoder data settings

The resolution of the absolute encoder is set via the parameter P605 "Absolute Encoder":

Parameter

Meaning

Availability

Setting example

P605 [-01]

Multi-turn resolution in bits

SK 530E and

above

12

4096 Encoder rotations

25Bit

encoder

P605 [-02]

Single-turn resolution in bits

SK 530E and

above

13

 8192

Steps per rotation

P605 [-03]

Sin/Cos periods per
rotation (Hiperface)

SK 540E and

above

Table 14: Parameter P605 - Setting of encoder resolution for absolute encoders

The relevant settings should be obtained from the data sheet for the absolute encoder.

The absolute encoder is activated via parameter P604 "Encoder Type". Here, a differentiation is made
between normal measurement (for "linear" systems) and "path optimised" measurement (for circulating
systems) (see Section 3.2.4).