POSICON position control for NORD frequency inverters, SK 530E and above

74

Subject to technical alterations

BU 0510 GB-3911

7.2.5

Miscellaneous encoder faults (universal encoder interface)

Symptom

Additional test

Possible cause

Hiperface encoders:

Motor has error E25.0 after starting

The Sin/Cos signals are not connected correctly.
The voltage signal can be checked with P709.

SSI encoders:

The position jumps back to 0 too
early.

Multiply Transmit (OFF),
PBF (OFF).

coding is in binary.

The resolution is set too low.

SSI encoders:

The position jumps instead of
counting up or down evenly.

Multiply Transmit (OFF),
PBF (OFF).

The position coding (Gray, binary) is not set
correctly.

The resolution is not set correctly, especially
with Gray coding.

SSI encoders:

The position jumps with a power
of 2.

Multiply Transmit (OFF),
PBF (OFF).

coding is in binary.

The resolution is set too high.

SSI encoders:

Continuous Multiply Transmit error

Encoder does not support Multiply Transmit

BISS encoder:

Communication error although the
encoder is connected.

Resolution set incorrectly

BISS encoder:

Communication error after enabling

Resolution set incorrectly

BISS encoder:

Ratio present, although none has
been set.

Resolution set incorrectly

Encoder reports an internal error.

If the encoder reports an internal error the cause
of the error must be determined from the reason
entered in parameter P650[-01] on the basis of
the documentation from the encoder
manufacturer.

A BISS encoder only reports a 1 as the cause of
the fault. This message means that a fault has
occurred since the last initialisation. If the fault
does not disappear of its own accord, the
encoder voltage supply must be disconnected
for 1 minute in order to reset the fault.

If the fault occurs after a long period of fault-free
operation this indicates that the encoder will
soon fail.

Universal encoder warning

The encoder reports and internal error P650[-01]
or an internal warning P650[-02]. However, the
fault is not critical for positioning.

A BISS encoder only reports a 1 as the cause of
the warning. This message means that a
warning has occurred since the last initialisation.
If the warning does not disappear of its own
accord, the encoder voltage supply must be
disconnected for 1 minute in order to reset the
message.

If the warning occurs after a long period of fault-
free operation this indicates that the encoder will
soon fail.