Parameter settings

BU 0510 GB-3911

Subject to technical alterations

43

Value Function

Description

Signal

With function P610 = 5 "Flying Saw", the slave returns to its starting
position and remains there until the next "Start Flying Saw" command.
A new start command is only accepted if the slave has reached its
starting position. The position setpoint (P602) of the master drive is
reset with the 0

1 flank.

01

Flank

64

Start Flying Saw

Start command for synchronisation of the slave drive with the master.

01

Flank

77

Stop Flying Saw

The "Flying Saw" function is interrupted. The slave drive stops and
remains in its present position, however it can be re-synchronised to
the master at any time with the command "Start Flying Saw".

01

Flank

Parameter
{factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter set

P434

Relay 1 function

(Function of output 1 (Relay 1

– MFR1))

up to SK 535E

P

0 ... 39

{ 1 }

Control terminals 1/2: The settings 3 to 5 and 11 work with a 10% hysteresis, i.e. the relay
contact closes (Function 11 opens) when the limit value is reached and opens (function 11 closes)
when a 10% smaller value is undershot. This behaviour can be inverted with a negative value in
P435.

Various functions can be programmed. These can be seen in the following table.

P434

[-01]

...

[-05]

Digital out function

(Function of digital outputs)

SK 540E and

above

P

0 ... 39

{ [-01] = 1 }

{ [-02] = 7 }

all other { 0 }

Up to 5 outputs (2 of which are relays), which can be freely programmed with digital functions are
available in the SK 54xE. These can be seen in the following table.

[-01] = Output 1 / MFR1, relay output 1: external brake, (default), Terminals 1/2

[-02] = Output 2 / MFR2, relay output 2: Fault, (default),

Terminals 3/4

[-03] = Output 3 / DOUT1, digital output 1: No function, (default), Terminal 5

[-04] = Output 4 / DOUT2, digital output 2: No function, (default), Terminal 7

7

[-05] = Output 5 / DOUT3, digital output 3: No function, (default), Terminal 27

7

NOTE

The standardisation assigned to output 1 by parameter P435 is deactivated with POSICON-
relevant functions (20 - 26).

The hysteresis assigned to output 1 by parameter P436 is deactivated with POSICON-relevant
functions (20 - 26). Parameterisation of the hysteresis can be jointly parameterised with regard
to POSICON-relevant functions for all outputs by means of parameter P625.

This also applies accordingly for the other digital and relay outputs of the inverter.

List of possible functions for the relays and digital outputs P434, P441, P450, P455
(only POSICON functions)

Details:

see Section 3.8

7

Digital input 7 (DIN7) can also be used as digital output 3 (DOUT3 / Binary output 5). It is recommended that either an input function (P420 [-07] or an

output function (P434 [-05]) is parameterised. However, if and input function and an output function are parameterised, a High signal from the output function
will result in the activation of the input function. This IO-exclusion is hence used as a kind of "flag". This also applies for digital input 8 (DIN8) and digital
output 2 (DOUT2 / binary output 4).