2 Encoder connections

The internal zero point of the inverter can be adjusted by specifying an offset value.

A possible reduction ratio between the position measurement system (encoder) and the motor can be taken
into account by the use of transformation and reduction ratios. The motor and the position measurement
system (encoder) do not need to have the same direction of rotation. A negative ratio must be set if the
direction of rotation is different.

2.1 Terminal blocks

The terminal blocks for the control connections and for the encoder differ between the versions and sizes of
the frequency inverter.

2.1.1

Terminal blocks SK 53xE Size 1

– 4




X6:

Incremental
encoder input
Encoder, e.g.: TTL,
10-30V, RS422,
2048
impulses/rotation

Note:

5V encoders should
not be used.

X7:

additional digital
inputs and outputs

DIP switch:

Switching from analog
inputs AIN2/AIN1
current/voltage
setpoint

I = current 0/4...20mA
V = voltage 0...10V

NOTE:

AIN2

– upper DIP

Switch
AIN1

– lower DIP

Switch

X8:

VI_S 24V, pulse block
input

VO_S 15/24V, output
for commissioning
without safety
switching device

only for SK 53xE

and not with 115VAC

devices

further details in

handbook BU 0530

X4:

analog inputs and
outputs

+10V max. 5mA

0...10V or

0/4...20mA

Analog output

: 0 …

10V

X5: digital inputs and

voltage supply

R

i DIN

approx. 4.5k


with SK 530E

Terminal 42internal

+15V max. 150mA

+5V max. 250mA

with SK 535E

Terminal 44external

+18-30V min. 800mA

X11:

1x RJ12 socket to
connect the RS232 or
RS485 interface

X9/X10:

2x RJ45 socket to
connect the
CAN/CANopen
interface

X9

X10

X11

Fig. 1: Terminal blocks, SK 53xE Size 1 - 4