4 extra functions – NORD Drivesystems BU0510 User Manual

Page 47

Advertising
background image

4

Parameter settings

BU 0510 GB-3911

Subject to technical alterations

47

4.4 Extra functions

Parameter
{factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter set

P502

[-01]

...

[-05]

Value Masterfunction

(Value Masterfunction)

S

P

0 ... 57

{ all 0 }

Selection of master values (up to SK 535E: max. 3 master values, SK 540 and above: max. 5
master values:

[-01] = Master value 1

[-02] = Master value 2

[-03] = Master value 3

SK 540E and above:

[-04] = Master value 4

[-05] = Master value 5

Selection of possible setting values for the master values (illustration of POSICON-relevant
functions):

6 = Actual position

Low word

7 = Setpoint position

Low word

10 = Actual position,

increment Low word

11 = Setpoint position,

increment Low word

12 = BusIO Out Bits 0-7

13 = Actual position

High word

14 = Setpoint position

High word

15 = Actual position,

increment High word

16 = Setpoint position,

increment High word

P503

leading func. output

(leading func. output)

S

0 ... 5

{ 0 }

For master-slave applications this parameter specifies on which bus system the master transmits
the control word and the master values (P502) for the slave. On the slave, parameters (P509),
(P510), (P546 )(… (P548)) define the source from which the slave obtains the control word and
the master values from the master and how these are to be processed by the slave.

0 = Off,

no output of control word and master values.

1 = USS,

Output of control words and master values to USS.

2 = CAN,

Output of control words and master values to CAN

(up to 250kBaud).

3 = CANopen,

Output of control words and master values to CANopen.

4 = System bus active,

no output of control word and master values, however

via the ParameterBox or NORD CON, all participants
which are set to System bus active are visible.

5 = CANopen+System bus active

Output of control word and master values on CAN open

via the ParameterBox or NORD CON, all participants
which are set on the System bus active are visible.

P514

CAN bus baud rate

(CAN baud rate)

0 ... 7

{ 4 }

Used to set the transfer rate (transfer speed) via the CANbus interface. All bus participants must
have the same baud rate setting.

Additional information is contained in the manual BU 0060 CAN/CANopen.

0 = 10kBaud

1 = 20kBaud

2 = 50kBaud

3 = 100kBaud

4 = 125kBaud

5 = 250kBaud

6 = 500kBaud

7 = 1MBaud * (test

purposes only)

*) Reliable operation cannot be guaranteed