POSICON position control for NORD frequency inverters, SK 530E and above

58

Subject to technical alterations

BU 0510 GB-3911

4.6 Information

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter set

P709

Voltage analog input 1

(Voltage analog input 1)

up to SK 535E

0.00 ... 10.00 V

Displays the measured analog input value 1.

P709

[-01]

...

[-10]

Analog input voltage

(Analog input voltage)

SK 540E and

above

0.00 ... 10.00 V

Displays the measured analog input value.

[-01] = Analog input 1: Analog input 1, integrated into the FI

[-02] = Analog input 2: Analog input 2, integrated into the FI

[-03] = External analog input 1, "External analog input 1": Analog input 1 of the first IO

extension (SK xU4-IOE)

[-04] = External analog input 2, "External analog input 2": Analog input 2 of the first IO

extension (SK xU4-IOE)

[-05] = External Analog input 1 2nd IOE, "External analog input 1 of the 2nd IOE": Analog

input 1 of the second IO extension (SK xU4-IOE)

[-06] = External analog input 2 2nd IOE, "External analog input 2 of the 2nd IOE": Analog

input 2 of the second IO extension (SK xU4-IOE)

[-07] = Analog function, Dig2, "Analog function of digital input 2": Analog function of digital

input 2 integrated into the FI.

[-08] = Analog function, Dig3, "Analog function of digital input 3": Analog function of digital

input 3 integrated into the FI.

[-09] = Encoder track A: Monitoring of the input signal of track A of an incremental encoder

(Terminal X6:51/52)

[-10] = Encoder track B Monitoring of the input signal of track B of an incremental encoder

(Terminal X6:53/54)

NOTE:

The voltage difference between tracks A and B can be measured with the aid of
parameter P709 [-09] and [-10]. If the incremental encoder is rotated the value of
both tracks must jump between -0.8V and 0.8V. For Hiperface encoders the voltage
ranges from -0.5V...0.5V. If the voltage only jumps between 0 and 0.8V the relevant
rack is faulty. It may be possible to determine the position with the incremental
encoder, but the interface is considerably more susceptible to faults. We recommend
that the encoder is replaced!

P744

Configuration

(Configuration level)

0000 ... FFFF (hex)

This parameter displays the devices integrated in the FI. Display is in hexadecimal code
(SimpleBox, ControlBox, Bus system).

The display is in plain text when the ParameterBox is used.

SK 500E … 515E

= 0000

SK 520E

= 0101

SK 530E … 535E

= 0201

SK 540E … 545E

= 0301