4.2 Speed control

Parameter
{factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter set

P300

Servo Mode

(Servo Mode)

SK 520E or

higher

P

0 ... 1

{ 0 }

This parameter activates speed control with speed measurement via an incremental encoder.
This leads to a very stable speed behaviour up to motor standstill.

0 = Off

1 = On

NOTE:

For correct function, an incremental encoder must be connected (see Section 2.2)

and the correct pulse number must be entered in parameter P301.

P301

Incremental encoder

(Incremental encoder resolution)

SK 520E or

higher

0 ... 17

{ 6 }

Input of the pulse-count per rotation of the connected encoder.

If the encoder rotation direction is not the same as the FI, (depending on installation and wiring),
this can be compensated for by selecting the corresponding negative pulse numbers 8...16.

0 = 500 pulses

1 = 512 pulses

2 = 1000 pulses

3 = 1024 pulses

4 = 2000 pulses

5 = 2048 pulses

6 = 4096 pulses

7 = 5000 pulses

8 = -500 pulses

9 = -512 pulses

10 = -1000 pulses

11 = -1024 pulses

12 = -2000 pulses

13 = -2048 pulses

14 = -4096 pulses

15 = -5000 pulses

16 = -8192 pulses

17 = + 8192 pulses

NOTE:

P301 is also significant for position control via incremental encoders for SK 530E and

above. The pulse number is set here if an incremental encoder is used for
positioning (P604=1).