5 positioning – NORD Drivesystems BU0510 User Manual

Page 50

Advertising
background image

POSICON position control for NORD frequency inverters, SK 530E and above

50

Subject to technical alterations

BU 0510 GB-3911

4.5 Positioning

Parameter
{factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter set

P600

Position Control

(Position control)

SK 530E and

above

S

P

0 ... 4

{ 0 }

Activation of positioning control (see also Section 3.6).

0 = Off, positioning control is disabled

1 = Linear ramp (Max. freq.),

positioning control using linear ramp with maximum

frequency

2 = Linear ramp (setpoint freq.),

positioning control using linear ramp with setpoint

frequency

3 = S-Ramp (Max. freq.),

positioning control using S-ramp with maximum

frequency

4 = S-Ramp (Setpoint freq.),

positioning control using S-ramp with setpoint

frequency

P601

Actual position

(Actual position)

SK 530E and

above

-

50000,000 …

50000,000 rev.

Shows the actual position.

P602

Act. Ref. position

(Actual setpoint position)

SK 530E and

above

-

50000,000 …

50000,000 rev.

Shows the actual setpoint position.

P603

Curr. position diff.

(Actual position difference)

SK 530E and

above

S

-

50000,000 …

50000,000 rev.

Shows the actual difference between the setpoint and actual position.