4 Parameter settings

For a detailed overview of all available parameters, please refer to the frequency inverter manual BU0500. The
following only lists selected parameters and parameters specific to the function of POSICON.

NOTE:

The structure of individual parameters for SK 53xE frequency inverters differs from those for the
SK 54xE version. Because of this, the relevant parameters descriptions are listed twice.

Abbreviations used:

FI = Frequency inverter

SW = Software version stored in P707.

S = Supervisor parameters are visible or hidden dependent on P003.

4.1 Operating display

Parameter
{factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter set

P001

Select of disp. value

(Selection of display value)

0 ... 65

{ 0 }

Selection of the operating display for a ControlBox /SimpleBox. (Illustration of functions relevant to
POSICON)

16 = Position setpoint Actual setpoint (setpoint position)

17 = Actual position: Actual position

50 = Actual position, incremental: Actual position value of incremental encoder

51 = Actual position, absolute or Actual position, CANopen: Actual position value of

CANopen absolute encoder

52 = Actual position difference Actual difference between setpoint and actual position

53 = Actual position difference, absolute/incremental: Actual position difference (see also

P631) between absolute encoder and incremental encoder

54 = Actual position difference, calculated/measured: Actual position difference (see also

P630) between the calculated and measured difference of an encoder

55 = Actual position value, universal encoder: Actual position value of universal encoder

(absolute encoders except CANopen) (SK540E and above)