SDAP Series PD 2 to PD 4 Drying and Conveying Systems

Right Bed In Regen Light

The

Right Bed In Regen

LED lights when the right bed is in regeneration.


Right Bed Heater Light

The

Right Bed Heater

indicator lights when the right bed regenerates and is in the heat-up

portion of the regeneration cycle.

Process Blower On Light

The

Process Blower On

indicator lights when the process blower energizes.


Process Heater On Light

The

Process Heater On

indicator lights when the process air heater is energized.


Low Compressed Air Light

The

Low Compressed Air

alarm indicator lights when the dryer compressed air supply drops

below 60 psi (413kPa/ 4.13 bars). Upon loss of compressed air, the pressure switch opens and
sends a signal to the PLC controller to shut down dryer operation. Dryer operation automatically
resumes when 80 psi (551 kPa/ 5.51 bars) air is restored.

High Temp Process Air Light

The

High Temp Process Air

alarm indicator lights when the temperature at the process air

thermocouple is above the high alarm set value. Upon high temperature alarm condition the
process heaters turn off, the process blower remain on.

The alarm mode and value are factory-set to track 25º above the process set point. The alarm
value is an upper-limit deviation above the process set point. When the temperature at the
process thermocouple returns to within the acceptable range, the alarm output de-energizes and
all heaters turn on again automatically.

High Temp Regen Air Light

The

High Temperature Regen Air

alarm indicator lights when the thermostat above the

regeneration heater assembly senses an abnormally high temperature.

The regeneration heaters shut down until the temperature falls below the alarm point. The
regeneration blower continues to run for cooling the heaters and desiccant bed. The alarm
condition clears when the temperature drops below the thermostat setpoint. The heaters re-
energize automatically.

High Dew Point Light

The

High Dew Point

alarm indicator lights when the process air delivery dew point exceeds a

dew point of -10

°F (-23°C).