SDAP Series PD 2 to PD 4 Drying and Conveying Systems

The rotary selector switches are located under the dial. Turn the lower right rotary selector
switch to set the time unit selection. By turning the screw, the time units will cycle between
seconds, minutes, hours, and ten (10) hours.

Turn the lower left rotary selector switch to set the time range selection. The dial digits appear in
the windows around the time setting knob. The dial digits change when different time ranges are
selected. Time ranges are 0-0.5, 0-1, 0-5 and 0-10.

Figure 12

Typical SDAP System Timer

MIN

OUT

POWER

OFF

Power indicator

timer operates,

lit when timer

Output indicator

Scale range

Time range

Operating mode

Operation mode
selector; factory-

Time setting knob

Time unit

Time unit selector

display window

set "A" On-Delay

display window

display window

selector

(red LED)

(green LED)

stops operating

Flashes when

Range Selection Table

Time Time

units

range

sec(onds)

min(utes)

hrs (hours)

10h (ten hours)

1.2

0.05 to 1.2

0.12 to 1.2

0.12 to 1.2

1.2 to 12

3

0.3 to 3

0.3 to 3

0.3 to 3

3 to 30

12

1.2 to 12

1.2 to 12

1.2 to 12

12 to 120

30

3 to 30

3 to 30

3 to 30

30 to 300

0 Instantaneous

output


4-12 Convey Dump Delay Setting

After the convey timer times out, the PLC will start a dump delay before allowing the convey
cycle to start again. The dump delay time is adjusted by jumper inputs into the PLC. The yellow
jumpers are wired into yellow terminal blocks located on the sub-panel. For example, a ten (10)
second dump delay would have a yellow jumper wired from a number four terminal to number
33 (PLC I/18) terminal. Terminals number 31 and 32 would have no jumpers. Dump delay time
is the same for both convey stations.