E5ck factory setting for dew point – Sterlco SDAP 90-225 CFM Series Drying and Conveying Systems User Manual

Page 63

Advertising
background image

SDAP Series PD 2 to PD 4 Drying and Conveying Systems

Page 63

E5CK Factory Setting for Dew Point

1. Make sure jumper setting for input type is set for Current Input (I), right jumper.

2. Return controller to housing.

3. Press the

Display Key for one (1) second to enter Menu Display.

4. Press the

Arrow Up to switch between menus.

5. To switch parameters within a menu, press

Arrow Up.

Figure 19

Setting List for Dew Point Controller, Part No. A0548567

Mode Parameter

Setting

range

Default

AEC setting

Protect SECr Security

0 to 6

1

3

Protect YEYP A/M Key Protect

ON/OFF

OFF

ON

Manual Manual MV

-5.0 to 105.0 %

0.0

Default

Level 0 SP Set Point

SP lower limit to upper limit EU

0

Default

Level 0 r-S Run/Stop

Run/Stop

Run

Default

Level 1 AL-1 Alarm Value 1

-1999 to 9999 EU

0

-10.0

°F/-23°C

Level 1 AL-2 Alarm Value 2

-1999 to 9999 EU

0

-10.0

°F/-23°C

Level 1 C-db Dead Band

-19.99 to 99.99%FS

0.00

Default

Level 1 HYS Hysteresis (Heat)

0.01 to 99.99% FS

0.10

Default

Level 1 CHYS Hysteresis (Cool)

0.01 to 99.99 FS

0.10

Default

Level 2 SPrU Sp Ramp Time Unit

M(Minutes)/H(Hours)

M

Default

Level 2 SPrt Sp Ramp Set Value

0 to 9999 EU

0

Default

Level 2 CnF Input Digital Filter

0 to 9999 SEC

0

Default

Level 2 ALH1 Alarm 1 Hysteresis

0.01 to 99.99%

0.02

Default

Level 2 ALH2 Alarm 2 Hysteresis

0.01 to 99.99%

0.02

Default

Level 2 Cn5H input shift upper limit

-199.9 to 999.9

°C

0.0 Default

Level 2 Cn5L input shift lower limit

-999.9 to 999.9

°C

0.0 Default