10 setting the high dew point alarm, 11 setting the convey timer and range selection – Sterlco SDAP 90-225 CFM Series Drying and Conveying Systems User Manual

Page 35

Advertising
background image

SDAP Series PD 2 to PD 4 Drying and Conveying Systems

Page 35

„ Set the shift on dew point set point to the highest process air moisture content you want to

allow before the dryer shifts air flow to the regenerated desiccant bed. The dew point
controller is set at the factory for -20ºF (-29ºC).

„ To change the dew point setting, press the

Up Arrow and

Down Arrow keys

to the shift point you want.

4-10 Setting the High Dew Point Alarm

The high dew point alarm is factory set for -10ºF (-23ºC). The high dew point alarm will
energize the “High Dew Point” light. Entering the Level 1 operating parameter changes the high
dew point alarm setting.

1. Press

once (keep the pressure on the button for about 1-1.5 seconds) in order to

switch between modes. Level 0 displays.

2. Press

to display Level 1.

Lu-1

displays.

3. Press

once more for about one to one and a half seconds. Now use short presses

until

AL-1

displays.

4. Press

and

to set the higher or lower value for the high dew point alarm.

5. Press

for about one to one and a half seconds. Level 1 displays.

6. Press

until Level 0 displays.

7. Press

for about one to one and a half seconds to go to Operating mode.

Note: The E5CK controller has several levels of securities to lock out access to parameters and

menu settings. If the controller will not allow you to change settings, see Section 6-8 on
Page 60 to set the E5CK security to access the function you need.


4-11 Setting the Convey Timer and Range Selection

Set the convey timer by rotating the large dial to the convey time you want. The time units is
factory set for seconds. The time range is factory set to 0-30 seconds. The operating mode is set
to A for on-delay. Remove the black cover to gain access to the time unit selector and the time
range selector.