SDAP Series PD 2 to PD 4 Drying and Conveying Systems

Figure 19

Setting List for Dew Point Controller Part No. A0548567 Cont’d.

Mode Parameter

Setting

range

Default

AEC setting

Setup

Cn-t Input Type

0 to 21

2

17

Setup

Cn-H Scaling Upper Limit

Scaling Lower Limit +1 to

9999 EU

-100

15

°F/-9C

Setup

Cn-L Scaling Lower Limit

-1999 to SP Setting Upper

Limit –0.1 EU

0

-40

°F/-40C

Setup

dP Decimal Point

0 to 3

0

Default

Setup

CnCE Parameter Initialize

Yes/No

No

Default

Setup

6Ut1 Control Output 1

Assignment

Heat/Cool/Alarm 1/Alarm 2/

Alarm 3/LBA

Heat COOL

Setup

6Ut2 Control Output 2

Assignment

Heat/Cool/Alarm 1/Alarm 2/

Alarm 3/LBA

AL-1 Default

SetUp

Sub 1 Auxiliary Output 1

Assignment

Alarm 1/Alm 2/Alm 3/LBA/S.

ERR/E333

AL-2 Default

Setup

ALt1 Alarm 1 Type

0 to 11

2

8

Setup

AL1n Alarm 1 open in alarm

NO/NC

NO

Default

Setup

ALt2 Alarm 2 Type

0 to 11

2

8

Setup

AL2n Alarm 2 open in alarm

NO/NC

NO

Default

Setup

6rEU Direct/Reverse

Operation

OR-R/OR-D OR-R

Default

Expansion SL-H Set Point Upper Limit

SP Lower Limit +1 to

Scaling Upper Limit

1300

15

°F/-9C

Expansion SL-L Set Point Lower Limit

Scaling Upper Limit to Sp

Lower Limit

-200

-40

°F/-40C

Expansion CntL PID/ON/OFF

PID/ON-OFF

PID

ON-OFF

Expansion

rESt Standby Sequence

Reset Setting Method

0/1 0

Default

Expansion

rEt Automatic Return of

Display Mode

0 to 99 SEC

0

Default