Grout the baseplate – Goulds Pumps CV 3196 i-FRAME - IOM User Manual

Page 35

Advertising
background image

Specified limits

A C-face adapter can attain a nominal alignment of 0.007 in. Total Indicated Runout (T.I.R.). However,
because of the stack-up of the machining tolerances of the various parts, the alignment can be as high as
0.015 inches TIR.
If high reliability (with shaft alignments of less than 0.002 in. (0.05mm)) is required for the pump, use a
foot-mounted drive unit on a precision-machined baseplate and perform a conventional alignment.

Grout the baseplate

Required equipment:

• Cleaners: Do not use an oil-based cleaner because the grout will not bond to it. See the instructions

provided by the grout manufacturer.

• Grout: Non-shrink grout is recommended.

1. Clean all the areas of the baseplate that will come into contact with the grout.
2. Build a dam around the foundation.
3. Thoroughly wet the foundation that will come into contact with the grout.
4. Pour grout through the grout hole into the baseplate up to the level of the dam.

When you pour the grout, remove air bubbles from it by using one of these methods:

• Puddle with a vibrator.
• Pump the grout into place.

5. Allow the grout to set.

1

7

6

2

3

4

5

1.

Baseplate

2.

Shims or wedges

3.

Grout

4.

Foundation

5.

Sleeve

6.

Dam

7.

Bolt

6. Fill the remainder of the baseplate with grout, and allow the grout to set for at least 48 hours.

1

5

4

2

3

1.

Baseplate

2.

Grout

3.

Foundation

4.

Dam

5.

Bolt

7. Tighten the foundation bolts.

Installation

Model CV 3196 i-FRAME Installation, Operation, and Maintenance Manual

33