M3400 series ratings – Lenze MC3000 Series User Manual
Page 14
10
13435743_EDBM301_v14 .0
M3400 SERIES RATINGS
MODEL
INPUT
OUTPUT
(400/480 Vac, 50 - 60 Hz)
(0 - 400/460 Vac)
MODEL
NUMBER
1
FOR MOTORS
RATED
INPUT
PHASE
NOMINAL
CURRENT
2
(AMPS)
POWER
(kVA)
NOMINAL
CURRENT
(AMPS)
POWER
(kVA)
HP
kW
M3410
1
0 .75
3
2 .8 / 2 .4
2 .0
2 .3 / 2 .0
1 .6
M3420
2
1 .5
3
4 .7 / 4 .1
3 .4
3 .9 / 3 .4
2 .7
M3430
3
2 .2
3
6 .6 / 5 .7
4 .7
5 .5 / 4 .8
3 .8
M3450
5
3 .7
3
10 .2 / 8 .9
7 .3
8 .7 / 7 .6
6 .1
M3475
7 .5
5 .5
3
14 .7 / 12 .8
10 .6
12 .6 / 11 .0
8 .8
M34100
10
7 .5
3
18 .3 / 15 .9
13 .2
16 .0 / 14 .0
11 .2
M34150
15
11
3
28 / 24
19 .8
24 / 21
16 .7
M34200
20
15
3
36 / 31
25 .3
31 / 27
21 .5
M34250
25
18 .5
3
44 / 38
31 .9
39 / 34
27 .1
M34300
30
22
3
52 / 45
37 .6
46 / 40
31 .9
M34400
40
30
3
68 / 59
49 .0
60 / 52
41 .4
M34500
50
37 .5
3
85 / 74
61 .5
75 / 65
51 .8
M34600
60
45
3
100 / 87
72 .3
88 / 77
61 .3
1
Refer to Section 3 for model number breakdown .
2