CONTROL WIRING

14 .1 GENERAL
14 .1 .1 kEYPAD CONTROL

The drive can be controlled by the keypad or by control devices wired to the terminal

strip . The drive will run from the keypad “out of the box”, as long as the factory jumper

between TB-1 and TB-2 is present, as shown below . If the jumper is not present, add

one, otherwise the drive will not start from the keypad . Refer to Section 13 - kEYPAD

CONTROL .

FACTORY JUMPER

1 2 5A 5B 6 10A

12A

RXA TXB

10B 2

13A 13B 13C 13D 14 15 2

16 17 18

14 .1 .2 CONTROL WIRING VS . POWER WIRING

External control wiring MUST be run in a separate conduit away from all other input and

output power wiring . If control wiring is not kept separate from power wiring, electrical

noise may be generated on the control wiring that will cause erratic drive behavior . Use

twisted wires or shielded cable grounded at the drive chassis ONLY . Recommended

control wire is Belden 8760 (2-wire) or 8770 (3-wire), or equivalent .
Torque the control terminals to 2 lb-in (0 .2 Nm) . Be careful not to overtorque the control

terminals, as this will cause damage to the terminal strip . This is not covered under

warranty and can only be repaired by replacing the control board .

14 .1 .3 TB-2: CIRCUIT COMMON

The TB-2 terminals are used as circuit common for the start/stop, input select, local/remote,

analog input, and analog output functions . There are three TB-2 terminals available on

the terminal strip, and they are all internally connected to each other on the main control

board . If necessary TB-2 may be connected to chassis ground .

NOTE
TB-2 MUST be connected to chassis ground when using serial

communications .

14 .1 .4 SURGE SUPPRESSION ON RELAYS

Current and voltage surges and spikes in the coils of contactors, relays, solenoids, etc,

near or connected to the drive, can cause erratic drive operation . Therefore, a snubber

circuit should be used on coils associated with the drive . For AC coils, snubbers should

consist of a resistor and a capacitor in series across the coil . For DC coils, a free-wheeling

or flyback diode should be placed across the coil . Snubbers are typically available from

the manufacturer of the device .