Lenze MC3000 Series User Manual

Page 40

Advertising
background image

36

13435743_EDBM301_v14 .0

15 .4

SPEED POT AND PRESET SPEED CONTROL

Shown below is the wiring diagram for a control scheme that utilizes a speed pot and

PRESET SPEEDS for speed control, and either a two-wire or three-wire START/STOP

circuit:

ST

OP

CIR
CUIT C

OMMON

0-10 VDC

INPUT

10 VDC

SUPPL

Y

CIR
CUIT C

OMMON

ST

AR

T

1 2 5A 5B 6 10A

12A

RXA TXB

10B 2

13A 13B 13C 13D 14 15 2

16 17 18

PRESE

T SPEED #3

SPEED POT

(10 k)

PRESE

T SPEED #1

PRESE

T SPEED #2

CIR
CUIT C

OMMON

The TB-2 terminals are internally tied together

NOTES:

1 . Program the PRESET SPEEDS (Parameters 1-4) to the desired values .
2 . Program TB-13A to select SPEED #1, TB-13B to select SPEED #2, and TB-13C

to select SPEED #3 (see Parameters 47, 48 and 49) .

3 . To select a preset speed, close the appropriate preset speed terminal to TB-2 .

To select SPEED #4, close any two of the preset speed terminals to TB-2 .

4 . For speed pot control, one of the TB-13 terminals needs to be programmed to

select 0-10 VDC . Close the selected TB-13 terminal to TB-2 for speed pot control .

This will result in the loss of one of the preset speeds .

5 . If none of the preset speeds (or the speed pot) are selected via contact closures,

the drive will default to keypad speed control .

Advertising