Fault messages – Lenze MC3000 Series User Manual

Page 76

Advertising
background image

72

13435743_EDBM301_v14 .0

FAULT MESSAGES

FAULT

DESCRIPTION

POSSIBLE CAUSES

EXTERNAL

External fault:

TB-13D is open or closed to

TB-2, depending on setting of

Parameter 50 - TB13D .

Check setting of Parameter 50 .

Check devices wired between

TB13D and TB-2 .

DB ERROR

Dynamic Brake fault:

DB circuit has sensed a resistor

overload .

The DB duty cycle is too high, causing

the resistors to overheat .

CONTROL

Control Board fault:

New software has been installed

that is different from the previous

version .

Perform a factory reset using

Parameter 65-PROGRAM .

This will update the software and allow

the fault to be reset .

INTERNAL

INTERN (#)

Internal fault:

The micro-processor has sensed

a problem .

Electrical noise on control wiring .

Defective microprocessor .

FOLLOWER

Loss of Follower fault:

4-20 mA signal at TB-5B is below

2 mA .

Parameter 55 - TB5B LOSS is

set to FAULT .

Blank Display

or repeatedly

flashes

TESTING

The power supply has shut down .

This can be the result of clogged

or failed heatsink fans .

Check heatsink fans (if equipped) .

Clear any obstructions .

If heatsinks are not clogged, contact

the Lenze AC Tech Service Department .