9 .1

INPUT VOLTAGE RATINGS

M3100 Series drives are rated for 240/120 Vac, 50-60 Hz input . The drive will function with

input voltage of 120 Vac (+10%, -15%) at 48 to 62 Hz when wired for 120 Vac input, or
with input voltage of 240 Vac (+10%, -15%), at 48 to 62 Hz, when wired for 240 Vac input .
M3200 Series drives are rated for 240/200 Vac, 50-60 Hz input . The drive will function
with input voltages of 200 to 240 Vac (+10%, -15%), at 48 to 62 Hz .
M3400 Series drives are rated for 480/400 Vac, 50-60 Hz input . The drive will function
with input voltages of 400 to 480 Vac (+10%, -15%), at 48 to 62 Hz .
M3500 Series drives are rated for 590/480 Vac, 50-60 Hz input . The drive will function

with input voltages of 480 to 590 Vac (+10%, -15%), at 48 to 62 Hz .
To select the proper input voltage on 240/200 VAC 30-60 Hp models, 400/480 VAC 75-

150 Hp and 480/590 VAC 75-150 Hp models the PL2 plug must be in the correct position .

PL2 is located either at the lower right corner, or upper right corner of the power board,

depending on horsepower . The PL2 plug is used to select the correct input voltage . Plug

PL2 into the top and middle pins to select 240, 480, or 590 VAC or the middle and bottom

pins to select 200, 400, or 480 .

NOTE:

In addition to the voltage plug selection, Parameter 0 – LINE VOLTS must also

be programmed for the proper voltage . Refer to Section 18 - DESCRIPTION OF

PARAMETERS .

Voltage Selection Plug (PL2)

MODEL

CODE

1200
1400
1500

200V

400V

480V

240V
480V
590V

240 / 480 / 590 Vac INPUT

MODEL

CODE

1200

1400

1500

200V

400V

480V

240V
480V
590V

200 / 400 / 480 Vac INPUT