Lenze MC3000 Series User Manual

Page 62

Advertising
background image

58

13435743_EDBM301_v14 .0

45

@ TB10B

(TERMINAL TB-10B SCALING)

This parameter scales the analog output signal at TB-10B . This setting is the load (in %)

that is indicated when the TB-10B output measures 10 VDC .
Example:

The drive is part of a control system that requires a 0-10 VDC signal to

indicate 0-150% drive load . If this parameter is set to 150%, the drive will

output 10 VDC at 150% load (and about 6 .7 VDC at 100% load) .

NOTE:

The output signal at TB-10B is affected by the setting of Parameter 34 - LOAD

MLT .

47

TB13A

(TB-13A INPUT FUNCTION)

This parameter is used to select the function of terminal TB-13A . Closing TB-13A to TB-2

activates the TB - 13A input function . The following functions can be selected:

NONE

Disables the TB-13A function .

0-10VDC

Selects 0-10 VDC as the AUTO speed reference input (or setpoint

source in PID mode) . The 0-10 VDC signal is wired to TB-5A

and TB-2 .

4-20 MA

Selects 4-20 mA as the AUTO speed reference input (or setpoint

source in PID mode) . The 4-20 mA signal is wired to TB-5B and

TB-2 .

SPEED#1

Selects PRESET SPEED #1 as the AUTO speed reference .

LOC SEL

Selects LOCAL mode when Parameter 30 - CONTROL is set to

TB STRIP . Drive is in REMOTE mode if contact closure is not

made .

DEC FREQ

Decrease frequency setpoint . Used with the MOP (motor operated

pot) function . Refer to Section 14 .2 .6 - SPEED REFERENCE
SELECTION .

48

TB13B

(TB-13B INPUT FUNCTION)

This parameter is used to select the function of terminal TB-13B . Closing TB-13B to TB-2

activates the TB - 13B function . The following functions can be selected:

NONE

Disables the TB-13B function .

0-10VDC

Selects 0-10 VDC as the AUTO speed reference input (or setpoint

source in PID mode) . The 0-10 VDC signal is wired to TB-5A

and TB-2 .

4-20 MA

Selects 4-20 mA as the AUTO speed reference input (or setpoint

source in PID mode) . The 4-20 mA signal is wired to TB-5B and

TB-2 .

SPEED#2

Selects PRESET SPEED #2 as the AUTO speed reference .

INC FREQ

Increase frequency setpoint . Used with MOP (motor operated

pot) function . Refer to Section 14 .2 .6 - SPEED REFERENCE

SELECTION .