Lenze MC3000 Series User Manual

Page 34

Advertising
background image

30

13435743_EDBM301_v14 .0

14 .2

START/STOP AND SPEED CONTROL

14 .2 .1 REMOTE MODE SELECTION

In order to respond to external START/STOP commands, the drive must be in the

REMOTE mode . The REMOTE mode can be selected by one of three methods on the

MC3000 drive:

1 . Program Parameter 30 - CONTROL to REMOTE .
2 . Program Parameter 30 - CONTROL to kEYPAD or kEYPAD 2, which activates

the LOCAL/REMOTE key on the keypad . Press the LOCAL/REMOTE key to

select REMOTE mode, and then press the ENTER key within three seconds .

3 . Program Parameter 30 - CONTROL to TB STRIP, and program the function of

terminal TB-13A or TB-13C (Parameter 47 or 49) to LOCAL SELECT . DO NOT

make a contact closure between TB-13A or TB-13C and TB-2 (making the contact

closure will select LOCAL mode) .

14 .2 .2 TWO-WIRE START/STOP CONTROL

A two-wire start/stop circuit can be accomplished as follows:

1 . Select REMOTE mode (see above) .
2 . Connect a jumper between TB-12A and TB-2 to provide a permanent START

command to the drive .

3 . Wire a normally open maintained contact between TB-1 and TB-2 . Close this

contact to RUN the drive and open this contact to STOP the drive .

Refer to the wiring diagram in Section 15 .2 .

14 .2 .3 THREE-WIRE START/STOP CONTROL

A three-wire start/stop circuit can be accomplished as follows:

1 . Select REMOTE mode (see above) .
2 . Wire a normally closed momentary STOP contact between TB-1 and TB-2 .

Momentarily open this contact to STOP the drive .

3 . Wire a normally open momentary START contact between TB-12A and TB-2 .

Momentarily close this contact to START the drive .

Refer to the wiring diagram in Section 15 .3 .

14 .2 .4 SPEED REFERENCE SIGNALS

The drive allows for three analog speed reference inputs: a speed potentiometer (10,000

Ohm), 0-10 VDC, or 4-20 mA .

SPEED POT

Connect the wiper to terminal TB-5A, and connect the high and

low end leads to terminals TB-6 and TB-2, respectively .

0-10 VDC

Wire the positive to terminal TB-5A and the negative to terminal

TB-2 . TB-5A input impedance is 200 kilohms .

4-20 mA

Wire the positive to terminal TB-5B and the negative to terminal

TB-2 . TB-5B input impedance is 100 ohms .

Advertising