Lenze MC3000 Series User Manual

Page 53

Advertising
background image

13435743_EDBM301_v14 .0

49

17

MOTOR OL

(MOTOR OVERLOAD)

The MC3000 Series is UL approved for solid state motor overload protection . Therefore,

a separate thermal overload relay is not required for single motor applications . The

MOTOR OVERLOAD circuit is used to protect the motor from overheating due to

excessive current draw .
The trip time for the MOTOR OVERLOAD is based on an “inverse I

2

t” function . This

function allows the drive to deliver 150% of the rated output current for one minute, and

even higher current levels for shorter periods of time . Once the overload circuit “times

out”, the drive will trip into an OVERLOAD fault .
The MOTOR OVERLOAD should be set to a value which is equal to the ratio (in

percentage) of the motor full load current rating to the drive output current rating . This

will result in an overload capacity of 150% of the MOTOR current rating for one minute .

If this parameter is set to 100%, the motor will be allowed to draw 150% of the DRIVE

output current rating for one minute . This distinction is important in cases where the motor

full load current rating is significantly less than the drive output current rating, such as

applications where the drive is oversized to meet torque requirements .
Example 1: A 5 Hp, 480 Vac drive is operating a 3 HP motor with a full load current

rating of 4 .8 amps . Divide the motor current rating by the drive output current

rating: 4 .8 / 7 .6 = 63% . Entering this value will allow continuous operation

at 4 .8 amps, and will also allow the motor to draw 7 .2 amps (150% of 4 .8

amps) for one minute . If the setting is left at 100%, the motor could draw

11 .4 amps (150% of 7 .6 amps) for one minute before faulting .

The MC Series drive has two options for thermal overload protection . One depends on the

speed of the drive, while the other does not . The diagram below illustrates the difference

between “speed compensated” and “non-compensated” thermal overload protection .

FREQUENCY (Hz)

M

AXIMUM C

ONTINUOUS

OUTPUT CURRENT (%)

NON-COMPENSATED

SPEED C

OMPENSA

TED

10

20

30

40

50

60

20

40

60

80

100

The “speed-compensated” thermal overload circuit offers additional protection from high

load conditions at low speeds, where motor cooling is often less effective (e .g ., motors

with shaft-mounted fans) . As seen on the diagram below, the drive reduces the allowable

continuous output current when operating at frequencies less than 30 Hz .

Advertising