Fx boost factory default settings – Lenze MC3000 Series User Manual

Page 55

Advertising
background image

13435743_EDBM301_v14 .0

51

FX BOOST FACTORY DEFAULT SETTINGS

HP

FACTORY

DEFAULT

HP

FACTORY

DEFAULT

0 .25 - 1

5 .30 %

15

2 .20 %

1 .5 - 2

4 .40 %

20

2 .00 %

3

3 .60 %

25

1 .80 %

5

3 .00 %

30

1 .60 %

7 .5

2 .70 %

40

1 .20 %

10

2 .40 %

50 - 60

0 .80 %

The diagram below illustrates how FX BOOST alters the V/Hz ratio to increase motor

torque .
The FX BOOST setting represents the amount of boost at 0 Hz (approximately 15% in the

example below), and as the output frequency approaches 30 Hz, the boost decreases to

zero . Therefore, at 30 Hz and above, the V/Hz ratio returns to its “normal” state .

OUTPUT FREQUENCY (Hz)

OUTPUT VOL

TA

GE

(%)

FX BOOST

CONSTANT V/Hz

10

20

30

40

50

60

10

20

30

40

50

60

70

80

90

100

22

TORQUE

(TORQUE CURVE SELECTION)

This parameter is used to select whether the output of the drive follows a constant or

variable V/Hz curve . The following selections are available:

CONSTANT

Use for constant torque applications to optimize torque .

VARIABLE

Use for variable torque applications to optimize energy savings .

CT / NOCMP

Use for constant torque applications that require full overload

capacity at low speeds (refer to Parameter 17 - MOTOR OL) .