TWO-WIRE START/STOP CONTROL

Shown below is the wiring diagram for a typical two-wire start/stop control scheme, using

one maintained contact (such as that from a PLC) for RUN and STOP commands . Close

the contact to RUN, and open the contact to STOP . Also shown is the wiring for a 0-10

VDC or 4-20 mA speed reference signal .

ST

OP

CIR
CUIT C

OMMON

0-10 VDC

INPUT

4-20 mA INPUT

CIR
CUIT C

OMMON

ST

AR

T FOR

W

ARD

MAINTAINED

RUN/STOP

CONTACT

1 2 5A 5B 6 10A

12A

RXA TXB

10B 2

13A 13B 13C 13D 14 15 2

16 17 18

ST

AR

T RE
VERSE

0-10 VDC or 4-20 mA

SELECT (see Note 3)

FWD

REV

(see Note 2)

The TB-2 terminals are internally tied together

NOTES:

1 . Close TB-1 to TB-2 to RUN, and open to STOP .
2 . If REVERSE direction is required, TB-13C must be set to START REVERSE

(refer to Parameter 49 - TB13C) . If REVERSE is not required, simply jumper

TB-12A to TB-2 .

3 . Program TB-13A, 13B, or 13C to select the appropriate speed reference signal

that will control the drive speed (refer to Parameters 47, 48, and 49) . When that

TB-13 terminal is closed to TB-2, the drive will respond to the selected speed

reference signal . In the diagram above, TB-13A is programmed to select either

a 0-10 VDC or 4-20 mA signal .

4 . If the contact closure is not made between TB-13A and TB-2 to select a speed

reference, the drive will default to keypad speed control .