Lenze MC3000 Series User Manual

Page 58

Advertising
background image

54

13435743_EDBM301_v14 .0

30

CONTROL

(START/STOP CONTROL)

This parameter selects the START/STOP control source, which is either the keypad

(LOCAL), the terminal strip (REMOTE), or the serial link (SERIAL) . The LOCAL/REMOTE

key on the keypad is also affected by the setting of this parameter . The following settings
are possible:
LOCAL

The drive will only respond to START/STOP commands from the keypad .

The LOCAL/REMOTE key is disabled .

REMOTE

The drive will only respond to START/STOP commands from the terminal

strip . The LOCAL/REMOTE key is disabled .

SERIAL

The drive will only respond to START/STOP commands through the serial

link .

kEYPAD

The LOCAL/REMOTE key on the keypad is enabled and is used to toggle

between LOCAL and REMOTE modes . Press the LOCAL/REMOTE key

to select the desired mode and then press the ENTER key within three

seconds .

NOTE: If LOCAL mode is selected, a jumper is required between TB-1

and TB-2 to allow the drive to START .

TB STRIP

The terminal strip is used to select LOCAL or REMOTE mode . LOCAL mode

if TB-13A or TB-13C is set for LOCAL SELECT and a contact closure is

made between TB-13A or TB-13C and TB-2 . If the contact closure is not

made, the drive will be in REMOTE mode .

kEYPAD 2

Acts the same as kEYPAD, but TB-1 is disabled as a STOP input when in

LOCAL mode . Therefore, a jumper is not required between TB-1 and TB-2

to START in LOCAL mode .

NOTE 1:

The STOP key on the keypad is always active . The STOP

input at TB-1 is active unless CONTROL is set to kEYPAD

2 and LOCAL mode is selected .

NOTE 2:

Refer to Parameter 70 - PID MODE for information on the

effects of LOCAL and REMOTE mode when operating the

drive in PID mode .

31

UNITS

(SPEED/PID UNITS)

This parameter sets the units of the output speed or the PID display on the keypad . The

following choices are available:

sp HERTZ

pid CFM

(cubic feet per minute)

sp RPM

(revolutions per minute)

pid GPM

(gallons per minute)

sp %HZ

(percent Hertz)

pid IN

(inches)

sp /SEC

(units per second)

pid FT

(feet)

sp /MIN

(units per minute)

pid /SEC

(units per second)

sp /HR

(units per hour)

pid /MIN

(units per minute)

sp GPH

(gallons per hour)

pid /HR

(units per hour)

NONE

(no units displayed)

pid F

(degrees Fahrenheit)

pid %

(percent of PID feedback)

pid C

(degrees Celsius)

pid PSI

(pounds per square inch)

pid MPM

(meters per minute)

pid FPM

(feet per minute)

pid GPH

(gallons per hour)

NOTE:

If one of the “pid” units is selected, but the drive is in MANUAL (open-loop)

speed control mode or PID MODE is DISABLED, the displayed speed units
will default to HERTZ .