53 hz 57% load – Lenze MC3000 Series User Manual

Page 74

Advertising
background image

70

13435743_EDBM301_v14 .0

19 .6

MC3000 DISPLAY IN PID MODE

When the drive is in PID mode, the DRIVE STATUS portion of the display will indicate

actual output frequency (in Hertz) instead of RUN, and the right side of the display will

indicate PID SETPOINT, % LOAD, or PID FEEDBACk . The ENTER key is used to toggle

between the different displays . Examples of the possible displays are shown below:

42.53 HZ 35.0 PSI

DRIVE

STATUS

PID

UNITS

PID

SETPOINT

42.53 HZ 57% LOAD

DRIVE

STATUS

PERCENT

LOAD

42.53 HZ 33.7 PSI

DRIVE

STATUS

PID

UNITS

PID

FEEDBACk

In the examples above, the drive is running at 42 .53 Hz to maintain the PID SETPOINT

of 35 .0 psi . Pressing the ENTER key displays % LOAD, which is 57% . Pressing ENTER

again displays the PID FEEDBACk from the process, which is 33 .7 psi .
When the PID SETPOINT and PID FEEDBACk displays are entered, the display will

flash SETPOINT or FEEDBACk before displaying the value to indicate which display

is being viewed .