Lenze MC3000 Series User Manual

Page 51

Advertising
background image

13435743_EDBM301_v14 .0

47

10

MIN FRQ

(MINIMUM FREQUENCY)

This parameter defines the lower limit of the drive’s speed range . MIN FRQ is used in
conjunction with MAX FRQ (Parameter 11 below) to define the operating range of the drive .
If MIN FRQ is set to a value above 0 .0 Hz, the drive will ramp up from 0 .0 Hz when given

a start command . Once running, however, the drive will not operate below the MIN FRQ

setting unless the rotation is changed, or a stop command is issued and the drive is

programmed to ramp to a stop .
If the MINIMUM FREQUENCY is set to 0 .0 Hz, the drive may be operated in ZERO SPEED

mode (drive is in RUN state, but there is no output to the motor) . ZERO SPEED operation

can be used in applications requiring the ability to start and stop the drive using only the

selected speed reference . The drive will start when the speed reference is raised above

0 VDC or 4 mA, and it will stop when the reference is lowered to 0 VDC or 4 mA . Note

that the drive must be initially started using one of the normal start commands (keypad
or terminal strip) .

11

MAX FRQ

(MAXIMUM FREQUENCY)

This parameter defines the upper limit of the drive’s speed range . MAX FRQ is used in

conjunction with MIN FRQ (Parameter 10 above) to define the operating range of the drive .

WARNING!
Consult motor manufacturer before operating motor above rated

frequency . Overspeeding the motor and/or driven equipment can

cause damage to equipment and injury to personnel!

12

DC BRAkE

(DC BRAkE VOLTAGE)

DC braking creates a braking torque by injecting DC voltage into the motor . This parameter

sets the magnitude of that DC voltage . The point at which the drive applies DC braking

to the motor depends on which STOP mode is programmed (either COAST or RAMP,

see Parameter 26 - STOP) .
If the drive is set to COAST, DC braking is activated when the stop command is given .

In this case, DC braking helps decelerate the motor . This is useful in applications where

a quick deceleration is desired on a load that would normally take a long time to coast

to a stop .
If the drive is set to RAMP, DC braking is activated when the output frequency reaches

0 Hz . In this case, the drive decelerates the load to a near stop and then DC braking is

used to stop and hold the motor . This is useful in applications where the load needs to

be stopped in a certain position . Similar applications with high-inertia loads utilize both

dynamic braking and DC braking . The dynamic braking allows the high-inertia load to be

decelerated quickly, while the DC braking stops the load in the desired position .
Due to heat generated in the motor, DC braking should only be used in applications

where the load is stopped infrequently . In high duty-cycle applications, dynamic braking is

recommended because the heat is dissipated through external resistor banks, rather than

in the motor . When used, DC BRAkE should be set to the lowest voltage that provides

satisfactory operation in order to minimize motor heating . The maximum voltage available

depends on the voltage rating of the drive .

Advertising