Maximum dc brake voltage – Lenze MC3000 Series User Manual

Page 52

Advertising
background image

48

13435743_EDBM301_v14 .0

Refer to the table below:

MAXIMUM DC BRAkE VOLTAGE

MODEL M3100

240 / 120 Vac

MODEL M3200

240 / 200 Vac

MODEL M3400

480 / 400 Vac

MODEL M3500

590 / 480 Vac

24 VOLTS

24 VOLTS

48 VOLTS

59 VOLTS

13

DC TIME

(DC BRAkE TIME)

This parameter determines the length of time that the DC braking voltage is applied to the

motor . DC TIME should be set to the lowest value that provides satisfactory operation

in order to minimize motor heating .
NOTE:

If this parameter is set to 999 .9 seconds (the maximum value), the DC braking

will be continuous . If it is set to .0 seconds, it is disabled .

14

DYN BRAkE

(DYNAMIC BRAkE)

This parameter enables the dynamic braking circuit . Set this parameter to ON only if the

optional dynamic braking circuit board and resistors are installed .
Dynamic braking is used in applications where high-inertia loads need to be decelerated

quickly . When this is attempted, the motor regenerates voltage back into the drive, causing

the DC bus voltage to rise, eventually resulting in a HI VOLTS fault . With the dynamic

braking option, the DC bus voltage is monitored, and when it reaches a certain level, a

transistor is switched on that connects an external resistor bank across the DC bus . This

allows the regenerated energy from the motor to be dissipated through the resistors as

heat, which keeps the DC bus voltage below the trip level .
16

CURRENT

(CURRENT LIMIT)

This parameter sets the maximum allowable output current of the drive, which also

determines the torque capability of the motor . For most applications, CURRENT is left

at the maximum setting, which is 150% or 180% (of the drive’s output current rating),

depending on whether the input voltage is low or high (refer to Parameter 0 - LINE VOLTS) .

Regardless of the CURRENT setting, the drive is capable of delivering a maximum of

150% current for one minute, and 180% current for approximately 30 seconds, before

tripping into an OVERLOAD fault . Refer to Parameter 17 – MOTOR OL .
The drive will enter current limit when the load demands more current than the drive can

deliver, which results in a loss of synchronization between the drive and the motor . To

correct this condition, the drive will enter FREQUENCY FOLDBACk, which commands

the drive to decelerate in order to reduce the output current and regain synchronization

with the motor . When the overcurrent condition passes, the drive will return to normal

operation and accelerate back to the speed setpoint . However, if FREQUENCY

FOLDBACk cannot correct the condition and the drive remains in current limit for too

long, it will trip on an OVERLOAD fault . If the drive enters current limit while accelerating,

the time required to reach the speed setpoint will be longer than the time programmed

into ACCEL (Parameter 8) .

Advertising