If the drive powers up correctly, follow the procedure given below to check the motor

rotation:

1 . Verify that there is a wire jumper between terminals TB-1 and TB-2 on the Main

Control Board . The drive should have this jumper from the factory . If it is not

present, add one, otherwise the drive will not start .

2 . Use the q key to decrease the speed setpoint to the minimum value allowed

(0 .50 Hz if Parameter 10 - MIN FRQ has not been changed) .

3 . Press the START key . The drive should indicate RUN, but if the speed setpoint

is 0 .50 Hz, the motor may not rotate . Press the p key to increase the speed

setpoint until the motor starts to rotate .

4 . If the motor is rotating in the wrong direction, press the STOP key and remove

power from the drive . Wait three minutes for the bus capacitors to discharge,

and swap any two of the motor wires connected to T1, T2, and T3 .

NOTE 1:

The drive is phase insensitive with respect to incoming line voltage .

Therefore, to change the motor rotation, the phases must be swapped at

the drive output terminals or at the motor .

NOTE 2:

If the drive's display is blank when power is applied, and the drive is equipped

with fans at the bottom of the heatsink, make sure the fans are spinning and

are free of any obstruction . If any of the fans are clogged with debris, it will

cause a blank display when power is applied .