Lenze MC3000 Series User Manual

Page 72

Advertising
background image

68

13435743_EDBM301_v14 .0

Example 1: A 0-100 psi transducer outputs a 4 mA signal at 0 psi and 20 mA at 100 psi .

Program Parameter 75 to 0 .0 PSI, and Parameter 76 to 100 .0 PSI (This

assumes that Parameter 31 - UNITS is set to pid PSI, and Parameter 33 -

UNITS DP is set to XXX .X) .

For a reverse acting transducer, set Parameter 75 - FB @ MIN to the maximum process

variable feedback value, and set Parameter 76 - FB @ MAX to the minimum process

variable feedback value . In other words, Parameter 75 is set higher than Parameter 76 .

See the example below:
Example 2: A 0-100 psi transducer outputs a 20 mA signal at 0 psi and 4 mA at 100 psi .

Program Parameter 75 to 100 .0 PSI, and Parameter 76 to 0 .0 PSI (This

assumes that Parameter 31 - UNITS is set to pid PSI, and Parameter 33 -

UNITS DP is set to XXX .X) .

19 .2

THE SYSTEM - DIRECT AND REVERSE ACTING

The entire system can also be direct or reverse acting . In a direct acting system, an

increase in motor speed causes an increase in the process variable . This is equivalent

to requiring an increase in motor speed in response to a decreasing process variable

feedback .
In a reverse acting system, an increase in motor speed causes a decrease in the process

variable . This is equivalent to requiring an increase in motor speed in response to an

increasing process variable feedback . Examples of direct and reverse acting systems

are described in the next section .

19 .3

PID CONTROL - DIRECT AND REVERSE ACTING

The PID Setpoint Control software can be direct or reverse acting, and must be set to

match the system . This is accomplished with Parameter 70 - PID MODE . When set to

NORMAL (for direct acting systems), the PID unit will command an increase in motor

speed if the process variable feedback decreases, and a decrease in motor speed if

the process variable feedback increases . When set to REVERSE (for reverse acting

systems), the opposite is true .
NOTE:

The REVERSE setting for Parameter 70 - PID MODE is not used to

compensate for reverse acting feedback devices . If a reverse acting feedback

device is used, program Parameters 75 and 76 as described above .

An example of a direct acting system is one that maintains duct pressure . Duct pressure

is the process variable that is monitored by the feedback device . As duct pressure rises,

motor speed needs to be decreased to maintain the pressure . A direct acting PID control

will command a decrease in motor speed in response to an increasing process variable

feedback .
An example of a reverse acting system is one that maintains water temperature in a

cooling tower . Water temperature is the process variable that is monitored by the feedback

device . As the water temperature rises, motor speed needs to be increased to lower the

temperature of the water . A reverse acting PID control will command an increase in motor

speed in response to an increasing process variable feedback .

19 .4

SETPOINT REFERENCE SOURCES

The setpoint reference input can be one of the following:
1 .

keypad

2 .

4-20 mA signal at TB-5B

3 .

0-10 VDC signal at TB-5A

4 .

Potentiometer signal at TB-5A

Advertising