13435743_EDBM301_v14 .0

61

MIN ALR

MIN ALARM - The relay de-energizes when the feedback signal

(in PID mode) or the speed reference signal (in open-loop speed

mode) equals or exceeds the MIN ALRM setting (Parameter 81),

and energizes when the signal falls below the MIN ALRM setting .

/ MIN ALR

INVERSE MIN ALARM - The relay energizes when the feedback

signal (in PID mode) or the speed reference signal (in open-

loop speed mode) equals or exceeds the MIN ALRM setting

(Parameter 81), and de-energizes when the signal falls below

the MIN ALRM setting .

MAX ALR

MAX ALARM - The relay de-energizes when the feedback signal

(in PID mode) or the speed reference signal (in open-loop speed

mode) is less than or equal to the MAX ALRM setting (Parameter

82), and energizes when the signal exceeds the MAX ALRM

setting .

/ MAX ALR

INVERSE MAX ALARM - The relay energizes when the feedback

signal (in PID mode) or the speed reference signal (in open-loop

speed mode) is less than or equal to the MAX ALRM setting

(Parameter 82), and de-energizes when the signal exceeds the

MAX ALRM setting .

REVERSE

The relay energizes when Reverse direction is selected, and

de-energizes when Forward direction is selected .

SLEEP

The relay energizes when the drive is in SLEEP MODE . See

Parameters 36 - 38 .

SPD = 0HZ

The relay energizes when there is no output to the motor, for any

reason, such as: drive is in STOP mode, drive is in RUN mode

but the speed command is 0 Hz, drive is in SLEEP mode, drive

has tripped into a fault, etc .

The open-collector output circuit is a current-sinking type rated at 30 VDC and 40 mA

maximum . An external power supply (30 VDC max .) must be used to power the open-

collector outputs . The drive does not have a power supply .

53

TB15 OUT

(TB-15 OPEN COLLECTOR OUTPUT)

This parameter sets the open-collector output indication for terminal TB-15 . It has the

same functionality as Parameter 52 - TB14 OUT above .

54

RELAY

(RELAY FUNCTION)

The control board has one set of FORM C relay contacts that can be programmed for

the same indications as the open-collector outputs described above .
The FORM C relay contacts on TB-16, 17, and 18 are rated 2 Amps at 28 VDC or 120

Vac . Control wiring diagrams show relays in the rest state (coils NOT energized) .

55

TB5B LOSS

(LOSS OF FOLLOWER ACTION)

This parameter selects the action taken by the drive if the follower signal is lost at TB-5B .

This function is only active if the follower signal is 4-20 mA . The signal is considered lost

if it falls below 2 mA .

NONE

The drive will go to the programmed minimum speed .

FAULT

The drive will trip into a FOLLOWER fault condition .

SP #4

The drive will go to SPEED #4 (Parameter 4) .