In order to use TB-5A or TB-5B for a setpoint input, one of the TB-13 terminals must

be programmed for the appropriate signal . Closing the TB-13 terminal to TB-2 will then

select that signal as the setpoint reference . If the contact closure is not made to TB-2,

the setpoint reference source will default to the keypad . Refer to Parameters 47 - TB13A,

48 - TB13B, and 49 - TB13C .
Remote setpoint reference inputs at TB-5A and TB-5B can only be used if that terminal

is NOT being used for the process feedback signal from a transducer . The MC3000

has only one analog input of each type, so the same type of signal cannot be used for

transducer feedback and setpoint reference . For example, a 4-20 mA signal from a

transducer could not be used as a feedback signal if the setpoint is being controlled by

a 4-20 mA signal from a PLC .

19 .5

TUNING THE PID CONTROL

Once the PID control is set up correctly, it needs to be tuned in order to maintain the

process setpoint . First, set the Integral and Differential Gains to zero, and increase the

Proportional Gain (Parameter 77) until the system becomes unstable, then lower the

gain until the system stabilizes again . Set the Proportional Gain about 15% less than

that value that stabilizes the system . If only Proportional Gain is used, and the system is

operating in a steady-state condition (setpoint is fixed and process variable has settled

to a fixed value), there will always be a certain amount of error in the system . This is

called the steady-state error .
Integral Gain (Parameter 78) is used to force the steady-state error to zero by increasing

the output speed command with respect to time . Over time, the error will be forced to

zero because the Integral term will continue to change the speed command, even after

the Proportional term reaches steady state and no longer affects the speed command .

The Integral Gain affects the rate of rise of the output speed command from the Integral

term . Small amounts of Integral Gain can cause large changes in PID performance, so

care must be taken when adjusting Integral Gain . Too much Integral Gain will result in

overshoots, especially if large step changes in error occur .
Typically, Proportional and Integral Gain are all that is needed to fine-tune the system .

However, it may be necessary to use Differential Gain (Parameter 79) to further stabilize

the system, especially when quick responses are required . The Differential term responds

to the rate of change of the error, not the actual error itself . Differential Gain acts like

a “shock-absorber” to dampen overshoots that can occur when the PID tries to react

quickly to changes in error or setpoint . This allows fast PID response, with reduced risk of

becoming unstable due to overshoots . The Differential term is very sensitive to electrical

noise on the feedback signal and to digitizing errors, so it must be used with caution .
The other parameter setting that affects the response of the PID control is Parameter

80 - PID ACC . This sets the acceleration (and deceleration) rate of the setpoint reference

into the PID unit . When the setpoint changes, this function will “filter” the input to the PID

unit by ramping the setpoint reference from the previous value to the new value . This will

help prevent overshoots that can occur when the PID control attempts to respond to step

changes in setpoint, resulting in smoother operation . If PID ACC is set to 0 .0 seconds,