Electrical installation

Wiring of system bus (CAN)

4

104

EDKCSEE040 DE/EN/FR 4.0

Bus cable length

Note!

The permissible cable lengths must be observed.

1. Check the compliance with the total cable length in Tab. 4-1.
The baud rate determines the total cable length.

CAN baud rate [kbit/s]

Max. bus length [m]

50

1500

125

630

250

290

500

120

1000

25

Tab. 4-1

Total cable length

2. Check the compliance with the segment cable length in Tab. 4-2.
The segment cable length is determined by the cable cross-section used and the

number of nodes. Without a repeater, the segment cable length corresponds to

the total cable length.

Number of nodes Cable cross-section

0.25 mm

2

0.5 mm

2

0.75 mm

2

1.0 mm

2

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

Tab. 4-2

Segment cable length

3. Compare the two values detected.
If the value detected from Tab. 4-2 is smaller than the total cable length to be

provided fromTab. 4-1 ,repeaters mustbe used.Repeaters dividethe totalcable

length into segments.