Electrical installation, Warnings, Danger – Lenze ECSEExxx User Manual

Page 86

Advertising
background image

Electrical installation

Power terminals

Mains connection

4

86

EDKCSEE040 DE/EN/FR 4.0

Fuses
Use the following circuit-breakers or UL-approved fuses to protect the mains

cable (see Fig. 4-2 ( 85)):

Power supply

module

Dimensioning according to IEC/EN

Dimensioning to UL

Circuit-breaker

Cable

cross-section

[mm

2

]

UL fuse

AWG

ECSxE012

C16 A

2.5

25A

12

ECSxE020

C16 A

2.5

25A

12

ECSxE040

:

C 40 A

10

1)

35 A

8

1)

/: , 

C 32 A

6

35 A

10

: 

C 40 A

6

2)

35 A

10

2)

: 

C 40 A

10

35 A

8

1) Cable without wire end ferrule or with pin-end connector

2) Cable length max. 30 cm

Warnings!

ƒ

Use UL-approved cables, fuses and fuse holders only.

ƒ

UL fuse:

– Voltage 500 ... 600 V

– Tripping characteristic ”H”, ”K5” or ”CC”

Replacing defective fuses

Danger!

Hazardous electrical voltage
Components can carry hazardous voltages up to 3 minutes after

power-off.
Possible consequences:

ƒ

Death or severe injuries when touching the device.

Protective measures:

ƒ

Replace fuses in the deenergised state only.

– Set controller inhibit (CINH) for all axis modules in DC-bus

operation and disconnect all power supply modules from the

mains.