Electrical installation

Power terminals

4

82

EDKCSEE040 DE/EN/FR 4.0

4.3

Power terminals

Danger!

Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when the device is touched in the event

of a fault.

Protective measures:

ƒ

Implement the actions required in the EN 61800-5-1. Especially:

– Fixed installation

– PE connection must conform to standards (PE conductor

diameter  10 mm

2

or PE conductor must be connected twice)

Stop!

No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:

ƒ

Destruction of the device if the mains voltage is too high.

Protective measures:

ƒ

Observe the maximally permissible mains voltage.

ƒ

Fuse the device correctly on the supply side against mains

fluctuations and voltage peaks.

ƒ

All power connections are plug connections and are coded. The connector

set for the ECSZE000X0B power supply modules must be ordered

separately.

ƒ

Installation of cables acc. to EN 60204-1.

ƒ

The cables used must comply with the approvals required for the

respective application (e.g. VDE, UL, etc.).