Electrical installation

Drive system on the mains

Electrical isolation

4

79

EDKCSEE040 DE/EN/FR 4.0

4.2

Drive system on the mains
This information applies to the ECS drive system, consisting of:

ƒ

ECSxE... power supply module

ƒ

ECSxK series capacitor module (optional)

ƒ

ECSxS/P/M/A series axis module

ƒ

Motor

ƒ

Accessories

ƒ

Wiring

4.2.1

Electrical isolation
The integrated electrical isolation between the power section and the control

section is a protective separation (reinforced insulation) acc. to EN 61800-5-1.
To maintain this protective separation, it must be ensured that the external

24 V supply and all components connected to this supply also have a protective

separation (SELV/PELV) acc. to EN 61800-5-1.

24 V supply

DC bus

X6/+24, GND

X22

Basic

insulation

(50 V)

Dig. input/output
X6/DI1, DI2, D24, DO1

Reinforced

insulation

(300 V)

Thermostat
X6/T1, T2

CAN
X4

Mains

AIF

X21

X1

Fig. 4-1

Electrical isolation