Electrical installation – Lenze ECSEExxx User Manual

Page 83

Advertising
background image

Electrical installation

Power terminals

4

83

EDKCSEE040 DE/EN/FR 4.0

Assignment of the plug connectors

Terminal

Function

Electrical data

X21

Mains connection

X21/L1

Mains phase L1

Dependent on application and

type

0 ... 480 V

up to 31.3 A (

70)

X21/L2

Mains phase L2

X21/L3

Mains phase L3

X21/PE

Connection of PE conductor

X22

DC-bus voltage connection

X22/BR0

Internal brake resistor, connection 1

Dependent on application and

type

0 ... 770 V

up to 38.5 A (

70)

X22/BR1

External brake resistor, connection 1

X22/+UG

Internal/external brake resistor, connection 2

X22/+UG

DC-bus voltage supply, plus

X22/-UG

DC-bus voltage supply, minus

X22/PE

Connection of PE conductor

Cable cross-sections and screw-tightening torques

Cable type Wire end ferrule

Possible cable

cross-sections

Tightening torque

Stripping length

Terminal strips X21 and X22

Rigid

0.2 ... 10 mm

2

(AWG 24 ... 8)

1.2 ... 1.5 Nm

(10.6 ... 13.3 lb-in)

5 mm for screw

connection

10 mm for spring

connection

Flexible

Without wire end

ferrule

0.2 ... 10 mm

2

(AWG 24 ... 8)

With insulated wire

end ferrule

0.25 ... 6 mm

2

(AWG 22 ... 10)

With insulated

TWIN wire end

ferrule

0.25 ... 4 mm

2

(AWG 22 ... 12)

Shielded cables
The following factors decisively determine the effect of the shielded cables:

ƒ

Good shield connection

Ensure a contact surface as large as possible

ƒ

Low shield resistance

Only use shields with tin-plated or nickel-plated copper braids (shields

with steel braids cannot be used).

ƒ

High overlap rate of the braid

At least 70 ... 80 % with 90° overlap angle

The ECSZS000X0B shield mounting kit includes a wire clamp and shield sheet.